GENLIS-R
H07V-R


No flame propagationNo fire propagation
CONDUCTOR
Copper, semi-rigid class 2
INSULATION
Polyvinyl chloride (PVC)

VOLTAGE
450/750 V

STANDARDS
HD 21.3 (CENELEC) - Design standard
EN 60332-1 - Flame propagation (single wire)
EN 50266 - Flame propagation (bunched wires)
IEC 60332-1 - Flame propagation (single wire)
IEC 60332-3 - Flame propagation (bunched wires)


APPLICATIONS AND MAIN CHARACTERISTICS
GENLIS-F cables are especially recommended for transporting power in domestic or industrial environments (offices, units, indoor wiring, signalling circuits, etc.), as they are installed in surface-mounted or built-in conductors or similar enclosed systems.

GENLIS-F cables are insulated by a thermoplastic mixture in two totally adhered concentric layers as per the SPEEDY-SKIN co-extrusion system for a lower friction factor and, therefore, maximum slide when drawing the cable inside the tube. This SUPERSLIDE property provides efficiency and time-saving during installation.

GENLIS-R cables are Non Flame-Propagating as per EN 50265 (corresponding to international standard IEC 60332-1). To the 6 mm2 section inclusive, they are also Non Fire-Propagating as per EN 50266 (corresponding to international standard IEC 60332-3).

GENLIS-F cables are certified with the AENOR-HAR trademark.

Maximum permanently-operating conductor temperature 70 ºC.

 Nominal SectionOverall DiameterWeightBending RadiusFree-air CurrentVoltage Drop 0.8Voltage Drop 1
 mm2mmkg/kmmmAV/A.kmV/A.km
11731061x1.52.925201320.1725.08
11731071x2.53.435251812.3915.36
11731081x43.95025237.7449.554
11731091x64.56530305.2016.383
11731101x105.811035403.1283.792
11731111x166.616540541.9962.383
11731121x258.226050701.2941.507
11731131x359.135055860.9551.086
11731141x5010.7480651030.7270.802
11731151x7012.367575--0.5260.555
11731161x9514.392590--0.40.4
11731171x12016.01160100--0.3320.317
11731181x15018.01430110--0.2830.257