HERSATENE
RHZ1 H-16 Al


No flame propagationLow acidity and corrosivity of emitted gases
CONDUCTOR
Aluminium, semi-rigid class 2
INSULATION
Cross-linked polyethylene (XLPE)
SCREEN
Copper wire helicoidal layer
SHEATH
Halogen-free thermoplastic polyolefine

VOLTAGE
26/45 kV

STANDARDS
IEC 60502.2 - Design standard
EN 50267 – Halogen free. Low corrosivity and acidity of evolved gases
IEC 60754 – Halogen free. Low corrosivity and acidity of evolved gases


APPLICATIONS AND MAIN CHARACTERISTICS
Cables for power distribution for medium voltage outdoor, cased or underground installations.

Abrasion and tear-resistant jacket. Easier slide.

Reticulating process: The three extruded layers (semi-conductors and insulation) are extruded at the same time in a triple head. The tube is kept under controlled inert gas (N2) pressure to prevent the formation of vacuoles. The temperature profile of the tube is carefully controlled to ensure the correct level of reticulation in the cable core.

Halogen-free cable.

 Nominal SectionDiameter Over InsulationOverall DiameterWeightBending RadiusFree-air CurrentBuried CurrentInductive reactanceCapacitance
 mm2mmmmkg/kmmmAAOhm/kmµF/km
12731169526.735.512605352652100.1340.165
127311712027.536.313405453052350.1270.187
127311815028.337.114355603402650.1230.203
127311918529.738.515755803902950.1160.227
127312024031.440.217706054603450.1110.254
127312130033.842.620256405303850.1080.292
127312240036.545.323606806154400.1030.335
127312350039.748.527457307104950.0980.378
127312463043.352.132757858305600.0950.419
127312580047.556.339158459606350.0910.466
1273126100051.960.7464091510857000.0890.506